Eaton 5PX G2 UPS
5PX G2 UPS features include:
Deployment simplified:Â The 5PX G2 UPS offers mass UPS firmware upgrades without dropping the load and provides an easy startup configuration wizard simplifying your UPS setup process.
Runtime:Â Increased standard runtime by at least 25% on 1.5 and 2 kVA models compared to the original 5PX UPS
Stay connected, securely: Reduce risk of intrusion with the optional Gigabit Network Card (NETWORK-M2), which is the first UPS connectivity device to meet both UL and IEC cybersecurity standards
Enhanced surge protection:Â The 5PX G2 provides enhanced surge protection keeping your branch offices and IT closets equipment safe
Quieter operation:Â The 5PX G2 utilizes less fans and the internal fans have the capability to completely turn off at less than 30% load when the unit is fully charged for improved energy efficiency and reduced noise pollution
-
Eaton 9395 UPS family
Power Xpert 9395 UPS
• Cost-effective and proven UPS solution
• Power rating: 225-1100 kVA
• Voltage: 480V and 400V
• Double conversion efficiency: 94%
• Lithium-ion battery options for longer operation life -
Eaton 9355 UPS
GENERAL DIAGNOSTICS Full system self-test at startup UPS BYPASS Automatic on overload or UPS failure PARALLEL FOR REDUNDANCY Yes, using Powerware Hot Sync technology and capacity DIMENSIONS AND WEIGHTS See product brochure OVERLOAD (NORMAL OPERATION) 150% for 5 sec / 125% for 1 min (online), 110% for 10 min ELECTRICAL INPUT NOMINAL INPUT VOLTAGE 9355 (10 – 15 kVA): 208V/120V or 220V/127V three-phase 400V models also available
9355 (20 – 30 kVA): 208V/120V, 220V/127V +10, -15% 480V/277V, 600V (480+600 with transformer) 400V models also available
INPUT VOLTAGE RANGE -15%, +10% from nominal at 100% load without depleting battery OPERATING FREQUENCY 50/60 Hz (45 to 65 Hz) INPUT POWER FACTOR 9355 (10 – 15 kVA): >0.99 typical, >0.96 frequency converter
9355 (20 – 30 kVA): 0.99 typical
INPUT CURRENT DISTORTION 5% THD ELECTRICAL OUTPUT NOMINAL OUTPUT VOLTAGEÂ 9355 (10 – 15 kVA): 208/120, 220/127 Vac
9355 (20 – 30 kVA): 208/120, 220/120 Vac
OUTPUT VOLTAGE REGULATION 9355 (10 – 15 kVA): ±1% static; ±5% dynamic at 100% resistive load change, <1 ms response time
9355 (20 – 30 kVA): ±1% static; ±4% dynamic with 100% step load recovery within 1 ms response time
EFFICIENCY 91%, typical HEAT DISSIPATION (BTU/HR) 10 kVA models:
3,798 @ 208V and 220V input
6,294 @ 480V and 600V (with input isolation transformer)15 kVA models: 5,122 @ 208V and 220V input
8,134 @ 480V and 600V (with input isolation transformer)20 kVA models:
6,762 @ 208V and 220V input
10,450 @ 480V and 600V (with input isolation transformer)30 kVA models:
9,220 @ 208V and 220V input
13,831 @ 480V and 600V (with input isolation transformer)BATTERY BATTERY TYPE 9 Ah, sealed, lead-acid, maintenance-free BATTERY RUNTIME See product brochure BATTERY MANAGEMENT ABM technology BATTERY REPLACEMENT Field-replaceable CHARGER 9355 (10 – 15 kVA): Default is 3.4A per battery string. Charger current is configurable from 0.5A to 25A per string with an overall maximum of 34A (limited by input current)
9355 (20 – 30 kVA): Default is 8A
START-ON-BATTERY Allows start of UPS without utility input COMMUNICATIONS LCD DISPLAY Graphical LCD with blue backlight LEDS (4) LEDs for notice and alarm AUDIBLE ALARMS Yes COMMUNICATION PORTS (1) RS-232, (1) relay contact, (1) REPO, (2) environmental input COMMUNICATION SLOTS (2) X-Slot communication bays POWER MANAGEMENT SOFTWARE Bundled software suite CD ENVIRONMENTAL OPERATING TEMPERATURE 50–104ºF (10–40ºC), 45ºC with 7.5% derating; Optimal battery performance: 77ºF (25ºC) STORAGE TEMPERATURE 32–77ºF (0–25ºC); Recommended battery storage: 59–77ºF (15–25ºC) RELATIVE HUMIDITY 9355 (10 – 15 kVA): 0–95%, non-condensing
9355 (20 – 30 kVA): 5–95%, non-condensing
AUDIBLE NOISE 9355 (10 – 15 kVA): <56 dBA at 1 meter (noiseless room) typical
9355 (20 – 30 kVA): <58 dBA at 1 meter depending on load
ALTITUDE 9355 (10 – 15 kVA): 9,843 ft. (3000m) without derating
9355 (20 – 30 kVA): <3000m
CERTIFICATIONS SAFETY CERTIFICATIONS UL1778 5th Edition, CSA C22.2 No. 107.3-14, NOM-NYCE EMC COMPLIANCE 47 CFR Part 15/ICES-003 Class A QUALITY ISO 9001:2015, ISO 14001:2004 SURGE ANSI C62.41 Category B3, IEC 61000-4-5 MARKINGS cULus, NOM-NYCE POWER DISTRIBUTION MODULE WITH MECHANICAL BYPASS SWITCH See product brochure OPTIONS See product brochure BUILT-IN CONNECTIVITY OPTIONS See product brochure