Eaton 93PM UPS
Product snapshot
10-400kW
480V, 415V, 400V, 380V, 220V, 208V
50/60 Hz
Double conversion with optional Energy Saver System (ESS)
Up to 97% in double conversion
Up to 99% in Energy Saver System
480V model: up to 8 internal power modules
208/220V model: up to 10 internal power modules
External parallel up to 8 UPSs
Tower
480V model: Internal batteries up to 50kW
415/400/380V model: Internal batteries up to 40kW
208/220V model: Internal batteries up to 60kW
External battery options for all models
Full tech specs
Power modules
10–200 kW in 5 kW increments at 208/220V
20–160 kW in 10 kW increments at 415/400/380V
20–200 kW in 10 kW increments at 480V
200–400 kW in 50 kW increments at 480V
Note: optional internal redundancy available for all models
General characteristics
Up to 99%
Up to 97%
Up to eight distributed. Some restrictions may apply; contact factory for more information.
Input characteristics | 480V models | 400V models | 208V models |
Voltage | 480/277V 4-wire 480V 3-wire |
380/220V 4-wire 400/230V 4-wire 415/240V 4-wire |
208/120V 4-wire 220/127V 4-wire |
Voltage range: | +10%/-15% | +10%/-10% | +15%/-15% @ 208V
+10%/-15% @ 220V |
Frequency range | 50/60 Hz | 50/60 Hz | 50/60 Hz |
Power factor | > .99 | > .99 | > .99 |
Input current distortion | < 3% @ 100% load capacity | < 3% @ 100% load capacity | ≤ 3.5% @ 100% load capacity |
Battery options | 480V models | 400V models | 208V models |
Battery voltage | 432V, 480V | 480V | 480V |
Charging method | ABM® or float technology | ABM® or float technology | ABM® or float technology |
Battery type | VRLA, AGM, Gel, Wet, Lithium, Flywheel, Super Caps | VRLA, AGM, Gel, Wet, Lithium, Flywheel, Super Caps | VRLA, AGM, Gel, Wet, Lithium |
Output | 480V models | 400V models | 208V models |
Voltage | 480 3-phase3-wire or 4-wire
208/120V with optional IAC-D, up to 200 kW |
380V, 400V or 415V 3-phase 3-wire or 4-wire |
208V or 220V 3-phase 3-wire or 4-wire |
Frequency range | 50/60 Hz | 50/60 Hz | 50/60 Hz |
Regulation | ±1% steady state | ±1% steady state | ±1% steady state |
Voltage THD | < 1% (100% linear load) < 5% (non-linear load) |
< 1% (100% linear load) < 5% (non-linear load) |
< 1% (100% linear load) < 5% (non-linear load) |
Load power factor range | Unity with the ability to support 0.8 leading to 0.8 lagging without de-rating | Unity with the ability to support 0.8 leading to 0.8 lagging without de-rating | Unity with the ability to support 0.8 leading to 0.8 lagging without de-rating |
Certification | 480V models | 400V models | 208V models |
Safety | UL 1778, cULus, UL 924 Emergency, UL 924 Auxiliary | UL 1778, cULus | UL 1778, cULus |
EMC | FCC Part 15 subpart B class A | FCC Part 15 subpart B class A | FCC Part 15 subpart B class A |
Surge | IEC 61000-4-5 | IEC 61000-4-5 | IEC 61000-4-5 |
Height: 74"
Depth: 42"
Width:
22”
- 20–150 kW (480V)\
- 20-120 kW (400V)
- 10–120 kW (208/220V)
32”
- 160–200 kW (480V)
- 120-160 kW (400V)
34.4"
- 10–160 kW (208/220V)
43.3"
- 10–200 kW (208/220V)
64"
- 250–400 kW (480V)
The 93PM meets the strict standards for UL 924 compliance for emergency lighting applications when ordered with an emergency lighting SKU. For more information, visit Eaton.com/UL924UPS.
• Integrated maintenance bypass
• Integrated distribution cabinet (with input and output transformer options)
• Integrated power distribution cabinet
• Integrated parallel tie cabinets
• Integrated battery cabinet (small and large)
• Wall-mounted or floor mounted bypass
• Lithium battery cabinet
• Custom options available. Contact factory for more information.
Eaton 93PM UPS
Easy deployment
● Simplifies installation by fitting perfectly in line or alongside any standard-depth rack
Ease of management
● Optimizes server virtualization through power management and connectivity software
● Increases uptime with 24×7 remote monitoring and reporting capabilities
Lowest Total Cost of Ownership (TCO)
● Conserves valuable data center floor space
● Reduces cost and unexpected future growth risks